A temperature controller based on STM8S105K4 — reads temperature via NTC thermistor, controls Heater/Cooler relays, displays on 4-digit 7-segment LED, and communicates with PLC via Modbus RTU/ASCII.
📦 Key Features
Feature
Description
Temperature measurement
NTC thermistor via 10-bit ADC, Steinhart-Hart equation
Temperature control
Heater / Cooler relays with hysteresis (delta)
Display
4-digit 7-segment LED (multiplexed)
PLC Communication
Modbus RTU / ASCII over UART2 (9600 baud)
Persistent config
Internal EEPROM (1 KB)
NTC calibration
Recalibrate coefficients A, B, C based on reference temperature
Pin Function Pin Function
──────────────────────── ────────────────────────
PA1 OSC IN PC1 LED digit 4
PA2 OSC OUT PC2 Seg G
PB0 Button 1 (Power) PC3 Seg C
PB1 Button 2 (Setting) PC4 Seg DP
PB2 Button 3 (Up ▲) PC5 Seg D
PB3 Button 4 (Down ▼) PC6 Seg E
PB4 ADC IN4 (NTC) PC7 Seg B
PB5 Relay Heat PD0 LED digit 3
PD1 SWIM (Debug) PD2 LED digit 2
PD5 UART2 TX PD3 Seg F
PD6 UART2 RX PD4 Seg A
PF4 Relay Cool PD7 LED digit 1
🎮 Button Guide
Button
Short Press
Long Press
BT1 (Power)
Exit setting / Reset show mode
Toggle display on/off (sleep)
BT2 (Setting)
Enter setting mode
Hold BT2 + ▲/▼ = select Fn → release = edit Fn
BT3 (▲)
Increase value / Switch mode
—
BT4 (▼)
Decrease value / Switch mode
—
Factory reset: Long press BT1 → reset all defaults (T=20°C, delta=3, addr=1, sample=3)
Display Mode (show_mode)
Mode
Display
Note
0
Current temperature (°C)
Default
1
Modbus slave address
Prefix A
2
Delta (hysteresis)
Prefix d
Setting Mode (setting_mode)
Mode
Setting
Prefix
1
Modbus slave address (1–99)
A
2
Delta / hysteresis (0–99)
d
3
Target temperature (setting_T)
—
4
Sample time in minutes (1–99)
S
5
Buffer_T — calibration offset
—
Auto-exits setting after 15 seconds of inactivity.